This Acti9 iID is a modular and reliable residual current device for electric vehicles. It is a 2P circuit breaker with a nominal current In of 40A, B-EV protection class, and a residual current sensitivity of 30mA.
This product provides protection against electric shocks from direct or indirect contact and fire hazards. It functions to disconnect electrical circuits in case of a grounding fault. The unique Visitrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on the front panel.
This product also features a VisiSafe window with a green strip on the button indicating full pole opening, allowing downstream maintenance. This product complies with IEC/EN 61008-2-1 and IEC/EN 62423 standards. The rated breaking and short-circuit capacity (Im/m) is 1500 A. The conditional short-circuit current (Inc/c) is 10 kA. The electrical lifespan is 15000 cycles. The mechanical lifespan is up to 20000 cycles. The operating voltage of the UPS is 230 VAC.